Current carrying capacities※1
(Ambient temperature other than 30℃) =※1 This calculation method applies only temperature correction factor. The adjustment factor may differ according to operating conditions. Please refer to NFPA70・NFPA79.
Size(AWG) | 1c |
14 | 30 |
12 | 35 |
10 | 50 |
8 | 70 |
6 | 95 |
4 | 125 |
2 | 170 |
1 | 195 |
2/0 | 265 |
3/0 | 310 |
4/0 | 360 |
250 MCM | 405 |
350 MCM | 505 |
400 MCM | 545 |
500 MCM | 620 |
Ambient temperature(℃) | Correction factor |
10 or less | 1.20 |
11 - 15 | 1.15 |
16 - 20 | 1.11 |
21 - 25 | 1.05 |
26 - 30 | 1.00 |
31 - 35 | 0.94 |
36 - 40 | 0.88 |
41 - 45 | 0.82 |
46 - 50 | 0.75 |
51 - 55 | 0.67 |
56 - 60 | 0.58 |
61 - 65 | 0.47 |
66 - 70 | 0.33 |