Current carrying capacities(A)※1
(Ambient temperature other than 30℃) =※1 This calculation method applies only correction factor by number of wires and temperature correction factor. The adjustment factor may differ according to operating conditions. Please refer to NFPA70. NFPA79.
Size(AWG) | 1c - 3c |
20 | 5 |
18 | 14 |
16 | 18 |
14 | 25 |
12 | 30 |
10 | 40 |
8 | 55 |
6 | 75 |
4 | 95 |
2 | 130 |
1 | 145 |
2/0 | 195 |
3/0 | 225 |
4/0 | 260 |
250 MCM | 290 |
350 MCM | 350 |
400 MCM | 380 |
500 MCM | 430 |
No. of cores | Correction factor |
4 - 6c | 0.80 |
7 - 9c | 0.70 |
10 - 20c | 0.50 |
21 - 30c | 0.45 |
31 - 40c | 0.40 |
41c and above | 0.35 |
Ambient temperature(℃) | Correction factor |
21 - 25 | 1.04 |
26 - 30 | 1.00 |
31 - 35 | 0.96 |
36 - 40 | 0.91 |
41 - 45 | 0.87 |
46 - 50 | 0.82 |
51 - 55 | 0.76 |
56 - 60 | 0.71 |
61 - 70 | 0.58 |
71 - 80 | 0.41 |