North America applicable cable

NORTH AMERICAApplicable cable

3TC (90℃ Dry)

  • Current carrying capacities(A)※1

    (Ambient temperature other than 30℃) =
  • 1Current carrying capacities applied by size and the number of cores
    x
  • 2Correction Factor by Number of wires(4c~)
    x
  • 3Temperature correction factor

※1 This calculation method applies only correction factor by number of wires and temperature correction factor. The adjustment factor may differ according to operating conditions. Please refer to NFPA70. NFPA79.

1Current carrying capacities(A) applied by size and the number of cores.(at30 deg., Ambient temperature)

Size(AWG) 2c - 3c
18 6
16 8
14 25
12 30
10 40
8 55
6 75
4 95
2 130

2Correction factor by number of wires(4c~)

No. of cores Correction factor
4 - 6c 0.80
7 - 9c 0.70
10 - 20c 0.50
21 - 30c 0.45
31 - 40c 0.40
41c and above 0.35

3Temperature correction factor

Ambient temperature(℃) Correction factor
10 or less 1.15
11 - 15 1.12
16 - 20 1.08
21 - 25 1.04
26 - 30 1.00
31 - 35 0.96
36 - 40 0.91
41 - 45 0.87
46 - 50 0.82
51 - 55 0.76
56 - 60 0.71
61 - 65 0.65
66 - 70 0.58
71 - 75 0.50
76 - 80 0.41
81 - 85 0.29

© 2020 NICHIGOH COMMUNICATION ELECTRIC WIRE CO.,LTD. All Rights Reserved.