Europe applicable cable

EUROPEApplicable cable

ECO CABLE SERIES

5Non-sheathed cables

Product list

Product name Size(mm2)
05Z1-K 0.14 - 0.75
07Z1-K 1.5 - 240

⇄ Swipe

Reference standard

IEC 60364-5-52
Low-voltage electrical installations –
Part 5-52: Selection and erection of electrical equipment – Wiring systems

  • Current carrying capacities(A)

    (Ambient temperature other than 30℃) =
  • 1Current carrying capacities of each size.
    x
  • 2Temperature Correction Factor

1Current carrying capacities(A) of each size.(At30 deg.,Ambient temperature,Air free)

Size(mm2) 1c Size(mm2) 1c
0.14 7.5 16 127
0.25 10 25 174
0.34 12 35 213
0.5 15 50 280
0.75 20 70 368
1.5 30 95 434
2.5 40 120 517
4 52 150 601
6 68 185 692
10 96 240 790

⇄ Swipe

2Temperature Correction Factor

Ambient temperature(℃) Correction Factor
21 - 25 1.05
26 - 30 1.00
31 - 35 0.94
36 - 40 0.88
41 - 45 0.82
46 - 50 0.75
51 - 55 0.67
56 - 60 0.58
61 - 70 0.33