Europe applicable cable

EUROPEApplicable cable

ECO CABLE SERIES

40.14mm2- 35mm2

Product list

Product name Size(mm2)
PURELEX100T(S) 0.14 - 0.34
PURELEX110T(S) 0.5 - 35
PURELEX300F(S) 0.14 - 0.34
PURELEX500F(S) 0.5 - 6.0

⇄ Swipe

Reference standard

IEC 60364-5-52
Low-voltage electrical installations –
Part 5-52: Selection and erection of electrical equipment – Wiring systems

  • Current carrying capacities(A)

    (Ambient temperature other than 30℃) =
  • 1Current carrying capacities applied by size and the number of cores.
    x
  • 2Temperature Correction Factor

1Current carrying capacities(A) applied by size and the number of cores.(At30 deg.,Ambient temperature,Air free)

Size(mm2) 2c 3c 4c 5c 6c 7c 8c 10c 12c 14c 16c 18c 20c 24c 32c 40c
0.14 4.4 3.7 3.2 3.0 2.8 2.7 2.6 2.4 2.2 2.1 2.0 1.9 1.9 1.8 1.6 1.5
0.25 6.1 5.1 4.5 4.2 4.0 3.8 3.6 3.3 3.1 3.0 2.8 2.7 2.7 2.5 2.3 2.2
0.34 7.5 6.2 5.6 5.2 4.9 4.7 4.5 4.2 3.9 3.7 3.5 3.4 3.3 3.1 2.8 2.7
0.5 9.3 7.8 7.0 6.5 6.2 5.9 5.8 5.3 5.0 4.7 4.5 4.4 4.2
0.75 13 11 10 9.4 9.0 8.6 8.4 7.7 7.1 6.8 6.5 6.3 6.1
1.5 19 16 15 14 13 12 12 11 10 9.8 9.4 9.1 8.9
2.5 27 23 21 19 18 18 17 16 15 13 13 13 13
4 37 31 29 27
6 46 38 35 33
10 60 51 46 43
16 75 64 58 54
25 97 82 75 70
35 116 98 89 83

⇄ Swipe

2Temperature Correction Factor

Ambient temperature(℃) Correction Factor
20 1.10
21 - 25 1.05
26 - 30 1.00
31 - 35 0.95
36 - 40 0.89
41 - 45 0.84
46 - 50 0.77
51 - 55 0.71
56 - 60 0.63
61 - 65 0.55
66 - 70 0.45

© 2020 NICHIGOH COMMUNICATION ELECTRIC WIRE CO.,LTD. All Rights Reserved.