Europe applicable cable

EUROPEApplicable cable

WORLD WIDE STANDARD CABLE SERIES

418AWG-2AWG

Product list

Product name Size
RO-FLEX 7700T(S) 18AWG - 2AWG

⇄ Swipe

Reference standard

IEC 60364-5-52
Low-voltage electrical installations –
Part 5-52: Selection and erection of electrical equipment – Wiring systems

  • Current carrying capacities(A)

    (Ambient temperature other than 30℃) =
  • 1Current carrying capacities applied by size and the number of cores.
    x
  • 2Temperature Correction Factor

1Current carrying capacities applied by size and the number of cores.(At30 deg.,Ambient temperature,Air free)

Size 2c 3c 4c 5c
18AWG 16 16 12 12
16AWG 19 19 15 15
14AWG 26 26 20 20
12AWG 36 36 28 28
10AWG 47 47 37 37
8AWG 64 64 51 51
6AWG 85 85 68 68
4AWG 115 115 92 92
2AWG 152 152 121 -

⇄ Swipe

2Temperature Correction Factor

Ambient temperature(℃) Correction Factor
10 1.22
11 - 15 1.17
16 - 20 1.12
21 - 25 1.06
26 - 30 1.00
31 - 35 0.94
36 - 40 0.87
41 - 45 0.79
46 - 50 0.71
51 - 55 0.61
56 - 60 0.50

© 2020 NICHIGOH COMMUNICATION ELECTRIC WIRE CO.,LTD. All Rights Reserved.