Europe applicable cable

EUROPEApplicable cable

WORLD WIDE STANDARD CABLE SERIES

10.25mm2- 0.75mm2

Product list

Product name Size(mm2) Product name Size(mm2)
RO-FLEX 1000T(S) 0.25 - 0.34 RO-FLEX 3000F(S) 0.25 - 0.34
RO-FLEX 1100T(S) 0.5 - 0.75 RO-FLEX 3300F(S) 0.5 - 0.75
RO-FLEX-PREMIUM-1100T(S) 0.5 - 0.75 RO-FLEX-3MDF 0.75 + 2.5
RO-FLEX 3MDT 0.75 / 0.75+2.5 RO-FLEX CMF 0.75 / 0.75+2.5
RO-FLEX 3MDTP-IDS 0.5 RO-FLEX 3300F(S)-MTW 0.5 - 0.75
RO-FLEX TC-MTW-T 0.75 / 0.75+2.5 RO-FLEX-6MDF-MTW 0.75+2.5
RO-FLEX CMT 0.75 / 0.75+2.5 RO-FLEX 22775F(DC) 0.5 - 0.75
RO-FLEX 22775T(DC) 0.5 - 0.75 RO-FLEX 22775F(AC) 0.5 - 0.75
RO-FLEX 22775T(AC) 0.5 - 0.75

⇄ Swipe

Reference standard

IEC 60364-5-52
Low-voltage electrical installations –
Part 5-52: Selection and erection of electrical equipment – Wiring systems

  • Current carrying capacities (A)

    (Ambient temperature other than 30℃) =
  • 1Current carrying capacities applied by size and the number of cores.
    x
  • 2Temperature Correction Factor

1Current carrying capacities applied by size and the number of cores.(At30 deg.,Ambient temperature,Air free)

Size(mm2) 1c 2c 3c 4c 5c 6c・7c 8‐10c 11‐14c 15‐20c 21c
0.25 5.0 4.0 3.5 3.3 3.0 2.8 2.5 2.3 2.0 1.5
0.34 6.0 4.8 4.2 3.9 3.6 3.3 3.0 2.7 2.4 1.8
0.5 8.0 6.4 5.6 5.2 4.8 4.4 4.0 3.6 3.2 2.4
0.75 11 8.8 7.7 7.2 6.6 6.1 5.5 5.0 4.4 3.3

⇄ Swipe

2Temperature Correction Factor

Ambient temperature(℃) Correction Factor
10 1.22
11 - 15 1.17
16 - 20 1.12
21 - 25 1.06
26 - 30 1.00
31 - 35 0.94
36 - 40 0.87
41 - 45 0.79
46 - 50 0.71
51 - 55 0.61
56 - 60 0.50

© 2020 NICHIGOH COMMUNICATION ELECTRIC WIRE CO.,LTD. All Rights Reserved.